LEGRAND MEGALINE
Single-phase modular UPS systems from 1.25 to 10 kVA
- Single-phase modular UPS systems
- Power from 1250 to 10000 VA
- VFI-111 on-line double conversion
- Adaptable, expandable and redundant solutions
- Easy and fast management and maintenance
- Low environmental impact (high efficiency and reduced footprint)
- UPS system in a single or double cabinet depending on the power
MEGALINE UPS is a single phase uninterruptible power supply with high frequency PWM technology, On Line Double Conversion type, modular architecture, with the possibility of N+X redundant configuration.
It delivers a rated power from 1250 to 10000VA, equipped with valve-regulated hermetic-type accumulator batteries, contained inside the UPS in a specific compartment or in one or more external cabinets.
Functions
- Wide voltage range and input frequency
- Operating frequency from 50 to 60 Hz with auto-recognition
- Frequency conversion 50 in – 60 out or vice versa
- Extension of the input frequency range for operation with power-supply units
- Operation in eco mode (energy-saving)
- Possibility to set on line mode with a minimum load rate
- Adjustable output voltage with 1V intervals from front panel
- Low level of noise
- Measures internal and external temperature
- Controls the ventilation in relation to the temperature and the load
- Designed for remote emergency switch-off
Characteristics
General characteristics Single cabinet | 3 103 42 3 103 46 3 103 50 | 3 103 43 3 103 47 3 103 52 | 3 103 44 3 103 48 3 103 54 | 3 103 45 3 103 49 3 103 56 |
Nominal power (VA) | 1250 | 2500 | 3750 | 5000 |
Active power (W) | 875 | 1750 | 2625 | 3500 |
Max. expansion (VA) | 5000 | |||
Max. expansion (W) | 3500 | |||
Technology | On-line double conversion VFI-SS-111 | |||
Architecture | Modular, expandable, N+X redundant with 1250 VA power cards,contained in a single cabinet | |||
Input characteristics | ||||
Nominal input voltage | 230 V | |||
Input voltage range | 184 V to 264 V at 100% load | |||
Minimum operating voltage | 100 V at 50% load | |||
THD of input current | < 3% | |||
Input power factor | > 0.99 at 20% load | |||
Input frequency | 50 Hz/60 Hz ± 2% autosensing | |||
Output characteristics | ||||
Output voltage | 230 V ± 1% | |||
Output frequency | 50 Hz/60 Hz synchronised | |||
THD of output voltage | < 1% with non-linear load | |||
Waveform | Sinusoidal | |||
Peak factor | 1:3 | |||
Efficiency | up to 92% | |||
Overload capacity | 300% for 1 s – 200% for 5 s – 150% for 30 s | |||
Backup time | ||||
Backup time (min) | 13 | |||
Extension of backup time | Yes | |||
Equipment | ||||
Bypass | Automatic, internally synchronised, static and electromechanical (for overloads and operating problems) | |||
Signalling and alarms | Wide screen with 4 alphanumeric lines, multi-coloured status indicator, audible signalling | |||
Communication ports | 1 RS 232 port, 2 logic level ports | |||
Communicator UPS software | Can be downloaded free of charge (after requesting an activation code) | |||
Protection | Electronic devices for protection against overloads, short-circuits and excessive battery discharge. Operation stops at end of backup time. Inrush current limiter on start-up. Sensor for correct neutral switching. Back-feed protection (electrical safety insulation of the input plug during battery-based operation). EPO (emergency power off) contact. | |||
I/O mains connection | German standard/terminal connector with universal multi-socket outlet (Italian/German standard) | |||
Mechanical characteristics | ||||
Net weight (kg) | 23,5 | 34 | 43 | 53 |
Dimensions W x H x D (mm) | 475 x 270 x 570 | |||
Installed power cards | 1 | 2 | 3 | 4 |
Free power expansion slots | 3 | 2 | 1 | - |
Installed battery kits | 1 | 2 | 3 | 4 |
Free backup time extension slots | 3 | 2 | 1 | - |
Ambient conditions | ||||
Ambient operating temperature (°C) | 0 to 40°C | |||
Protection index | IP 21 | |||
Relative humidity (%) | 20 to 80% | |||
Noise at 1 m (dBA) | < 40 | |||
Certifications | ||||
Reference product standards | EN 62040-1, EN 62040-2, EN 62040-3 |
General characteristics Double cabinet | 3 103 60 + 3 107 78 | 3 103 63 + 3 107 79 | 3 103 66 + 3 107 80 | 3 103 69 + 3 107 81 | 3 103 72 + 3 107 82 |
Nominal power (VA) | 5000 | 6250 | 7500 | 8750 | 10000 |
Active power (W) | 3500 | 4375 | 5250 | 6125 | 7000 |
Max. expansion (VA) | 10000 | ||||
Max. expansion (W) | 7000 | ||||
Technology | On-line double conversion VFI-SS-111 | ||||
Architecture | Modular, expandable, N+X redundant with 1250 VA power cards,contained in a single cabinet | ||||
Input characteristics | |||||
Nominal input voltage | 230 V | ||||
Input voltage range | 184 V to 264 V at 100% load | ||||
Minimum operating voltage | 100 V at 50% load | ||||
THD of input current | < 3% | ||||
Input power factor | > 0.99 at 20% load | ||||
Input frequency | 50 Hz/60 Hz ± 2% autosensing | ||||
Output characteristics | |||||
Output voltage | 230 V ± 1% | ||||
Output frequency | 50 Hz/60 Hz synchronised | ||||
THD of output voltage | < 1% with non-linear load | ||||
Waveform | Sinusoidal | ||||
Peak factor | 1:3 | ||||
Efficiency | up to 92% | ||||
Overload capacity | 300% for 1 s – 200% for 5 s – 150% for 30 s | ||||
Backup time | |||||
Backup time (min) | 13 | ||||
Extension of backup time | Yes | ||||
Equipment | |||||
Bypass | Automatic, internally synchronised, static and electromechanical (for overloads and operating problems) | ||||
Signalling and alarms | Wide screen with 4 alphanumeric lines, multi-coloured status indicator, audible signalling | ||||
Communication ports | 1 RS 232 port, 2 logic level ports | ||||
Communicator UPS software | Can be downloaded free of charge (after requesting an activation code) | ||||
Protection | Electronic devices for protection against overloads, short-circuits and excessive battery discharge. Operation stops at end of backup time. Inrush current limiter on start-up. Sensor for correct neutral switching. Back-feed protection (electrical safety insulation of the input plug during battery-based operation). EPO (emergency power off) contact. | ||||
I/O mains connection | German standard/terminal connector with universal multi-socket outlet (Italian/German standard) | ||||
Mechanical characteristics | |||||
Net weight (kg) | 24 + 50 | 26,5+57,5 | 29 + 65 | 31,5+72,5 | 34 + 80 |
Dimensions W x H x D (mm) | 2 x 475 x 270 x 570 | ||||
Installed power cards | 4 | 5 | 6 | 7 | 8 |
Free power expansion slots | 4 | 3 | 2 | 60 | - |
Installed battery kits | 4 | 5 | 6 | 7 | 8 |
Free backup time extension slots | 6 | 5 | 4 | 3 | 2 |
Ambient conditions | |||||
Ambient operating temperature (°C) | 0 to 40°C | ||||
Protection index | IP 21 | ||||
Relative humidity (%) | 20 to 80% | ||||
Noise at 1 m (dBA) | < 40 | ||||
Certifications | |||||
Reference product standards | EN 62040-1, EN 62040-2, EN 62040-3 |
ORDERING INFORMATIONS
Avaibles Modules Single cabinet (German standard) | |||||
Cat. No. | Nominal power (VA) | Active power (W) | Back-up time (min) | Number of cabinets | Weight (kg) |
3 103 50 | 1250 | 875 | 13 | 1 | 23,5 |
3 103 52 | 2500 | 1750 | 13 | 1 | 34 |
3 103 54 | 3750 | 2625 | 13 | 1 | 43 |
3 103 56 | 5000 | 3500 | 13 | 1 | 53 |
Avaibles Modules Double cabinet | |||||
Cat. No. | Nominal power (VA) | Active power (W) | Back-up time (min) | Number of cabinets | Weight (kg) |
3 103 60 + 3 107 78 | 5000 | 3500 | 13 | 2 | 24+50 |
3 103 63 + 3 107 79 | 6250 | 4375 | 13 | 2 | 27+58 |
3 103 66 + 3 107 80 | 7500 | 5250 | 13 | 2 | 29+65 |
3 103 69 + 3 107 81 | 8750 | 6125 | 13 | 2 | 32+73 |
3 103 72 + 3 107 82 | 10000 | 7000 | 13 | 2 | 34+80 |
Avaibles Modules Single cabinet (French standard) | |||||
Cat. No. | Nominal power (VA) | Active power (W) | Back-up time (min) | Number of cabinets | Weight (kg) |
3 103 42 | 1250 | 875 | 13 | 1 | 23.5 |
3 103 43 | 2500 | 1750 | 13 | 1 | 34 |
3 103 44 | 3750 | 2625 | 13 | 1 | 43 |
3 103 45 | 5000 | 3500 | 13 | 1 | 53 |
Avaibles Modules Single cabinet (British standard) | |||||
Cat. No. | Nominal power (VA) | Active power (W) | Back-up time (min) | Number of cabinets | Weight (kg) |
3 103 46 | 1250 | 875 | 13 | 1 | 23.5 |
3 103 47 | 2500 | 1750 | 13 | 1 | 34 |
3 103 48 | 3750 | 2625 | 13 | 1 | 43 |
3 103 49 | 5000 | 3500 | 13 | 1 | 53 |
Avaibles Modules Single cabinet - without batteries | ||||
Cat. No. | Nominal power (VA) | Active power (W) | Back-up time (min) | Number of cabinets |
3 103 51 | 1250 | 875 | - | 1 |
3 103 53 | 2500 | 1750 | - | 1 |
3 103 55 | 3750 | 2625 | - | 1 |
3 103 57 | 5000 | 3500 | - | 1 |
Avaibles Modules Double cabinet - without batteries | ||||
Cat. No. | Nominal power (VA) | Active power (W) | Back-up time (min) | Number of cabinets |
3 103 60 + 3 108 59 | 5000 | 3500 | - | 2 |
3 103 63 + 3 108 59 | 6250 | 4375 | - | 2 |
3 103 66 + 3 108 59 | 7500 | 5250 | - | 2 |
3 103 69 + 3 108 59 | 8750 | 6125 | - | 2 |
3 103 72 + 3 108 59 | 10000 | 7000 | - | 2 |
- LEGRAND MEGALINE Brochure (1584.7 kB)
- LEGRAND MEGALINE 1250 Datasheet (208.3 kB)
- LEGRAND MEGALINE 2500 Datasheet (208.2 kB)
- LEGRAND MEGALINE 3750 Datasheet (207.7 kB)
- LEGRAND MEGALINE 5000 Datasheet (207.2 kB)
- LEGRAND MEGALINE 5000/2 Datasheet (195.3 kB)
- LEGRAND MEGALINE 6250/2 Datasheet (190.1 kB)
- LEGRAND MEGALINE 7500/2 Datasheet (190.4 kB)
- LEGRAND MEGALINE 8750/2 Datasheet (190.5 kB)
- LEGRAND MEGALINE 10000/2 Datasheet (190.0 kB)
Kunden, die diesen Artikel gesehen haben, sahen auch